Make Up Water In Cooling Tower ◆
Assume 0.01% of circulation for well-maintained towers: D = 1000 × 0.0001 = 0.1 gpm
| Parameter | Ideal Range | Why it matters | |-----------|-------------|----------------| | | 50–400 ppm (as CaCO₃) | Scale formation at high pH/temp | | Total alkalinity | < 400 ppm (as CaCO₃) | Decomposes to CO₂, lowers pH | | pH | 6.5–8.5 | Corrosion <6.5, scaling >8.5 | | Chlorides | < 500 ppm | Pitting corrosion (especially stainless steel) | | Silica | < 150 ppm | Hard, glass-like scale | | TSS | < 50 ppm | Fouling, sediment | | Iron | < 0.5 ppm | Staining, fouling | | Bacteria | No legionella or E. coli | Health risk (Legionnaires' disease) | make up water in cooling tower
M = E + B + D = 15 + 3.75 + 0.1 = 18.85 gpm Rule of thumb: Make-up ≈ 1.5–2.5% of circulation rate for most HVAC towers; higher for industrial (more blowdown). 4. Water Quality Requirements Poor make-up water causes scaling, corrosion, or biological growth. Assume 0
Controlled by cycles of concentration (COC). B = E / (COC – 1) If COC = 5, then B = 15 / (5-1) = 3.75 gpm 8.5 | | Chlorides | <